UAH
The combined device of protection against pulse retension type and 1+2 flp-12,5 v/3, flp-12,5v/3s in Odessa online-store Izoteh i Ko, OOO | Buy The combined device of protection against pulse retension type and 1+2 FLP-12,5 V/3, FLP-12,5V/3S Odessa (Ukraine) | Izoteh i Ko, OOO : Allbiz
Premium Standard
Reviews: 9
Izoteh i Ko, OOO
+38 (094) 945-70-57

The combined device of protection against pulse retension type and 1+2 FLP-12,5 V/3, FLP-12,5V/3S

The combined device of protection against pulse retension type and 1+2 FLP-12,5 V/3, FLP-12,5V/3S
  • The combined device of protection against pulse retension type and 1+2 FLP-12,5 V/3, FLP-12,5V/3S
In stock
Brand:Saltek
Country of manufacture:Czech Republic
Payment:
Shipping:
  • Customer pickup,
  • Courier,
  • Transport company
  • In detail
Description
The replaced varistorny module, the visual alarm system of fault

3-polar varistorny UZIP for installation in low-voltage distributing devices on border of the zones ZMZ0A - ZMZ 1 and the subsequent. Serves for prevention of the pulse retension caused by a lightning stroke and also switching retension.

The remote signaling is provided optionally (S).

Technical parameters

  • The rated voltage of Un is 230 V AC
  • The maximum operating voltage of Uc is 275 V AC/350 of V DC
  • Nominal discharge current (8/20 microsec) of In of 30 kA
  • Maximum discharge current (8/20 microsec) of Imax of 60 kA
  • Pulse discharge current (10/350mks) Iimp of 12,5 kA
  • Protection level on tension of Up 1,2 kV
  • Reaction time of ta is 25 nanoseconds
  • Short circuit protection at the maximum protection on current of 35 kArms
  • The maximum protection on current of 160 gL/gG
  • Class of protection of IP 20
  • Operating range of temperatures is -40 °C. +80 °C
  • Setting point DIN rail of 35 mm
  • Cross-section of connecting conductors
  • Single min/max ISO: 1/50 mm2; AWG: 17/1
  • Multicore min/max ISO: 1/35 mm2; AWG: 17/2
  • It is long cleaning of a wire of 14 mm
  • Torsion torque of max 4 Nm
  • Visual fault signaling Indicator of red color
  • Remote indication * the Potential-free replaced contact
  • Contacts of the remote signaling of 250 V/0,5 A AC, 250 V/0,1 A DC
  • Cross-section of conductors of the max 1,5 remote signaling of mm2
  • Compliance with requirements of the EN 61643-11 standard + A11 T1 T2
Characteristics:
Brand:Saltek
Country of manufacture:Czech Republic
Voltage: 230 V
Protective functions:Totally Enclosed
Information is up-to-date: 13.12.2019